HV Diagnostics HVA34TD VLF/DC Hipot Tester with Tan Delta Canada

HVA34TD

VLF/DC Hipot Tester with Integrated Tan Delta

Our HVA series HVA34 is arguably the top selling VLF/DC instrument on the market, so we added Tan Delta diagnostics to sweeten the deal! This combination allows the user to employ a VLF Hi-potential test while observing Tan Delta diagnostics.

Having the additional onboard diagnostic gives an inside look to the condition of the cable’s insulation. We preload this unit with test sequences that comply with the IEEE 400.2 standard, so cable testing has never been easier.

The HVA34TD-1 accommodates maintenance testing requirements for 25kV rated cables and below as per the latest revision of IEEE400.2 testing standard.

A single piece design, weighting only 86 pounds, this unit rolls like a suitcase for easy transport and comes with everything you need to test cable including corona suppression donuts, ground cable, High voltage test lead, simple test interfaces, etc.

Features:

  • Test your 25 (Maint), 15, 11, 8, 6.6, 5kV long MV cables
  • Weighs only 44lbs / 19.5kg
  • Perform tests fully automatically
  • Oscilloscope Display of Output Waveform
  • Insulation Resistance & Cap. Measurement
  • RMS Metering of Current and Voltage
  • Output Frequency optimization
  • Internal Storage of Test Reports
  • Download to PC and / or USB flash drive
  • Unlimited duty cycle
  • Flashover voltage detection
  • Bright backlit LCD display
  • Power supply immunity and independence
  • Low maintenance, oil-free design

Output Modes

  • VLF Sinewave / Squarewave & DC outputs
  • VLF 24kVrms / 34kVpk output
  • DC ±34kV
  • Cable Jacket / Sheath testing
  • Vacuum Bottle testing

Safety

  • Integrated internal discharge of DUT
  • Short circuit detection
  • 12kV power frequency voltage feedback protection
  • Remote interlock “kill switch” and HV status indication


Optional Attachments


 

Technical Specifications

Ordering Information:
707 003
Power Supply/Input Voltage:
100 to 240V AC ±10% (50/60Hz)
Input Power Requirements:
1.2kVA
Rated Max Output Voltage:
Sinusoidal RMS/Peak
24kV/34kV
Squarewave
34kV
DC
±34kV
Rate Max Output Current:
Sinusoidal RMS
10mA
DC/Squarewave
14.5mA
Output Frequency (default 0.1Hz):
0.01Hz to 0.1Hz in steps of 0.01 Hz
Frequency Optimization:
Yes
Maximum Output Load Capability @ MAXIMUM voltage and/or frequency:
0.5 µF
*120,000ft
*37km
Maximum Output Load Capability @ REDUCED voltage and/or frequency:
12 µF
*120 000ft
*37km
Metering:
Voltage
0.1kV Resolution ±1% Accuracy
Current
1 µA Resolution ±1% Accuracy
Capacitance
0.1 nF to 20 µF Range
Resistance
0.1MΩ to 20GΩ Range
Timing
Included and integrated
Fast Arc/Flashover
Detection Included and Integrated
Waveform
Real time oscilloscope display of actual output voltage waveform
Output Mode (all load independent & symmetrical):
VLF AC Sinewave
VLF AC Squarewave
DC (both Positive and Negative Polarity)
Fault Condition Mode / Fault Trip Mode
Vacuum Bottle Test Mode (DC) - optional
Cable Jacket / Sheath Test Mode
Output Duty:
Continuous
Computer Interface:
RS232 Standard, USB Flash Memory Download Module (optional)

HVA Control Center Software included with every HVA instrument
Memory / Test Record Storage:
Built in Memory
50 Test Records
USB Flash Drive
Unlimited (see options)
No. of programmable Automatic Test Sequences:
40
Standard HV Test Lead Cable Included:
13ft / 4m
Weight:
44 lbs / 20 kg
Dimensions:
Imperial (inches)
17 x 14 x 10"
Metric (mm)
430 x 360 x 250 mm
Environmental:
Storage
-13°F to 158°F / -25°C to 70°C
Operating
23°F to 113°F / -5°C to +45°C
Humidity
85% RH non-condensing

* Based on typical MV cable. 100pf/ft or 330 pF/m

Note: Due to continuous development, the information may change without notice.