HV Diagnostics HVA120 VLF / DC Hipot Tester Canada

HVA120 VLF / DC Hipot Tester

This single-piece design is an easy set up in the field. The associated reporting software has the versatility to not only report test results but also creates and loads test sequences onto the unit itself so you can complete your test with one click!

This unit has a real time oscilloscope display that gives other test parameters such as load capacitance and charging current and its user interface is extremely straightforward with a single rotary control and intuitive menu options.

The HVA120 unit can store up to 50 test reports that are accessible either through the optional USB interface or the standard RS232 connection. Simplify and automate your cable testing experience with this HVA Series system!

Features >>>

  • Tests your HV and Transmission cable networks
  • Test up to 5µF (50,000ft / 15kms)
  • Single Piece Design
  • Portable with weight of 436 lbs / 198 kg
  • Perform tests fully automatically
  • Real time oscilloscope display
  • RMS Metering of Current and Voltage
  • Output Frequency optimization
  • Insulation Resistance & Cap. measurement
  • Internal Storage of Test Reports
  • Download to PC and / or USB flash drive
  • Unlimited duty cycle
  • Bright backlit LCD display
  • Power supply immunity and independence
  • Low maintenance, oil-free design
  • HVA Control Center – User friendly software for immediate, professional detailed reporting and setup
  • Free HVA Control Center Software and upgrades

Output Modes >>>

  • High voltage 120kV (HVA120)
  • DC ±100 kV
  • VLF Sinewave / Squarewave & DC outputs
  • Cable Jacket / Sheath testing
  • Vacuum bottle testing
  • Fault Conditioning / Fault Trip
  • Load independent output waveform

Safety >>>

  • Integrated internal discharge of DUT
  • 12kV power frequency voltage feedback protection
  • Flashover voltage detection
  • Remote interlock “kill switch” and HV status indication
  • Short circuit detection
  • Local Emergency off button


Optional Attachments

Technical Specifications

Ordering Information:
712 001
Power Supply/Input Voltage:
110 to 240V AC ±10% (50/60Hz)
Input Power Requirements:
1.5kVA@120V (limited) 3kVA @240V
Rated Max Output Voltage:
Sinusoidal RMS/Peak
85kV / 120kV
Squarewave
100kV
DC
±100kV
Rate Max Output Current:
Sinusoidal RMS
60mA
DC/Squarewave
60mA
Output Frequency (default 0.1Hz):
0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies)
Frequency Optimization:
Yes
Maximum Output Load Capability @ MAXIMUM voltage and frequency:
0.5 µF
*5,000ft
*1.5km
Maximum Output Load Capability @ REDUCED voltage and/or frequency:
5 µF
*50,000ft
*15km
Metering:
Voltage
0.1kV Resolution ±1% Accuracy
Current
1 µA Resolution ±1% Accuracy
Capacitance
0.1 nF to 20 µF Range
Resistance
0.1MΩ to 20GΩ Range
Timing
Included and integrated
Fast Arc/Flashover
Detection included and integrated
Waveform
Real time oscilloscope display of actual output voltage waveform
Output Mode (all load independent & symmetrical):
VLF AC Sinewave
VLF AC Squarewave
DC (both Positive and Negative Polarity)
Fault Condition Mode / Fault Trip Mode
Vacuum Bottle Test Mode (DC) - optional
Cable Jacket / Sheath Test Mode
Output Duty:
Continuous
Computer Interface:
RS232 Standard, USB Flash Memory Download Module (optional)

HVA Control Center Software included with every HVA instrument
Memory / Test Record Storage:
Built in Memory
50 Test Records
USB Flash Drive
Unlimited (see options)
No. of programmable Automatic Test Sequences:
40
Standard HV Test Lead Cable Included:
20ft / 6m
Weight:
436 lbs / 198 kg
Dimensions:
Imperial (inches)
31 x 17.5 x 29"
Metric (mm)
790 x 445 x 740 mm (excluding handle)
Environmental:
Storage
-13°F to 158°F / -25°C to 70°C
Operating
23°F to 113°F / -5°C to +45°C
Humidity
85% RH non-condensing

* Based on typical MV cable. 100pf/ft or 330 pF/m